This is the ESPHome configuration I use for my two Kincony N30 energy monitors, along with a full reference of the N30's Modbus registers and coils.

For updating the N30's ARM firmware from Linux, see Flashing the Kincony N30 ARM Firmware from Linux.

IotaWatt and two N30s on DIN rail inside the monitoring enclosure

ESPHome Configuration

Kincony provides an ESPHome YAML for the N30:

My configuration is based on the newer version. The differences:

  • The shared settings (Wi-Fi, API, OTA, MQTT, time, restart buttons, etc.) come from my common package. See ESPHome Common for how that is laid out.
  • Buttons to clear the energy counters on each chip (coils 520-522).
  • No command_throttle.
  • The 30 channels are templated, instead of written out one sensor at a time.

Templating

ESPHome YAML does not have loops. But, !include with vars, plus math in substitutions, gets close. The config is split into four files:

File Contents
components/kincony-n30-channel.yaml Current, power and energy for one channel.
components/kincony-n30-chip.yaml One BL0910 chip: includes the channel file 10 times, plus the sum, voltage, frequency, temperature and power factor, and the clear-energy button.
devices/kincony-n30.yaml The N30 board: ESP32-S3, UART to the ARM CPU, OLED display, Modbus controller, and the chip file 3 times.
n30.yaml One device. Just the substitutions, and the device file.

The register addresses are calculated from the chip's base address. For channel ch on a chip starting at base:

  • Current: base + (ch - 1) * 2
  • Power: base + 20 + (ch - 1) * 2
  • Energy: base + 40 + (ch - 1) * 2

The device file includes each chip, with its number and base address:

packages:
  common: !include ../common/package-common.yaml
  chip1: !include { file: ../components/kincony-n30-chip.yaml, vars: { prefix: "${devicename}", chip: 1, base: 100 } }
  chip2: !include { file: ../components/kincony-n30-chip.yaml, vars: { prefix: "${devicename}", chip: 2, base: 200 } }
  chip3: !include { file: ../components/kincony-n30-chip.yaml, vars: { prefix: "${devicename}", chip: 3, base: 300 } }

And, the config for each board is just this (plus the commented-out override examples below):

substitutions:
  devicename: n30
  friendly_name: n30

packages:
  device: !include devices/kincony-n30.yaml

My second N30 is the same file, with n31 instead of n30.

esphome config on the templated version resolves to the same 107 sensors and 5 buttons as the original, hand-written file. Both boards are running it.

components/kincony-n30-channel.yaml
# One CT channel. vars: prefix, chip, ch, base
sensor:
  - platform: modbus_controller
    address: ${ base + (ch - 1) * 2 }
    register_type: holding
    name: ${prefix|upper}_${chip}_${ch}_current
    id: ${prefix}_${chip}_${ch}_current
    unit_of_measurement: A
    device_class: current
    accuracy_decimals: 3
    value_type: U_DWORD_R
    filters:
      - multiply: 0.001

  - platform: modbus_controller
    address: ${ base + 20 + (ch - 1) * 2 }
    register_type: holding
    name: ${prefix|upper}_${chip}_${ch}_power
    id: ${prefix}_${chip}_${ch}_power
    unit_of_measurement: W
    device_class: power
    accuracy_decimals: 1
    value_type: S_DWORD_R
    filters:
      - multiply: 0.1

  - platform: modbus_controller
    address: ${ base + 40 + (ch - 1) * 2 }
    register_type: holding
    name: ${prefix|upper}_${chip}_${ch}_energy
    id: ${prefix}_${chip}_${ch}_energy
    unit_of_measurement: kWh
    device_class: energy
    state_class: total_increasing
    accuracy_decimals: 3
    value_type: FP32_R

components/kincony-n30-chip.yaml
# One BL0910 chip: 10 channels plus chip-level readings. vars: prefix, chip, base
packages:
  ch1: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 1
      base: ${base}
  ch2: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 2
      base: ${base}
  ch3: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 3
      base: ${base}
  ch4: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 4
      base: ${base}
  ch5: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 5
      base: ${base}
  ch6: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 6
      base: ${base}
  ch7: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 7
      base: ${base}
  ch8: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 8
      base: ${base}
  ch9: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 9
      base: ${base}
  ch10: !include
    file: kincony-n30-channel.yaml
    vars:
      prefix: ${prefix}
      chip: ${chip}
      ch: 10
      base: ${base}

sensor:
  - platform: modbus_controller
    address: ${ base + 60 }
    register_type: holding
    name: ${prefix|upper}_${chip}_11_energy_d
    id: ${prefix}_${chip}_11_energy_d
    unit_of_measurement: kWh
    device_class: energy
    state_class: total_increasing
    accuracy_decimals: 3
    value_type: FP32_R

  - platform: modbus_controller
    address: ${ base + 62 }
    register_type: holding
    name: bl0910_${chip}_voltage
    id: ${prefix}_${chip}_voltage
    unit_of_measurement: V
    device_class: voltage
    accuracy_decimals: 1
    value_type: U_WORD
    filters:
      - multiply: 0.01

  - platform: modbus_controller
    address: ${ base + 63 }
    register_type: holding
    name: bl0910_${chip}_frequency
    id: ${prefix}_${chip}_period
    unit_of_measurement: Hz
    device_class: frequency
    accuracy_decimals: 2
    value_type: U_WORD
    filters:
      - multiply: 0.01

  - platform: modbus_controller
    address: ${ base + 64 }
    register_type: holding
    name: bl0910_${chip}_tps1
    id: ${prefix}_${chip}_tps_1
    unit_of_measurement: "°C"
    device_class: temperature
    accuracy_decimals: 1
    value_type: FP32_R

  - platform: modbus_controller
    address: ${ base + 66 }
    register_type: holding
    name: bl0910_${chip}_power_factor
    id: ${prefix}_${chip}_power_factor
    device_class: power_factor
    accuracy_decimals: 2
    value_type: FP32_R

button:
  - platform: template
    name: ${prefix|upper}_${chip}_clear_energy
    entity_category: config
    on_press:
      - lambda: |-
          id(${prefix}_modbus)->queue_command(modbus_controller::ModbusCommandItem::create_write_single_coil(id(${prefix}_modbus), ${ 519 + chip }, true));

devices/kincony-n30.yaml
# Kincony N30: ESP32-S3 + ARM CPU with 3 BL0910 chips (30 CT channels).
# Requires substitutions: devicename, friendly_name.
# Register map: https://www.kincony.com/forum/showthread.php?tid=8644
packages:
  common: !include ../common/package-common.yaml
  chip1: !include { file: ../components/kincony-n30-chip.yaml, vars: { prefix: "${devicename}", chip: 1, base: 100 } }
  chip2: !include { file: ../components/kincony-n30-chip.yaml, vars: { prefix: "${devicename}", chip: 2, base: 200 } }
  chip3: !include { file: ../components/kincony-n30-chip.yaml, vars: { prefix: "${devicename}", chip: 3, base: 300 } }

esp32:
  board: esp32-s3-devkitc-1
  framework:
    type: arduino

logger:
  # baud_rate: 0

# Network: Wi-Fi uses DHCP through the shared common package.
# Ethernet is preserved here for later hardware testing:
# ethernet:
#   type: W5500
#   clk_pin: GPIO42
#   mosi_pin: GPIO43
#   miso_pin: GPIO44
#   cs_pin: GPIO41
#   interrupt_pin: GPIO2
#   reset_pin: GPIO1

# Board pin map (vendor documentation):
#   I2C: SDA GPIO18, SCL GPIO17
#   LoRa SPI: SCK GPIO13, MOSI GPIO12, MISO GPIO11, CS GPIO14,
#             RST GPIO21, DIO0 GPIO47
#   SD SPI: MOSI GPIO40, SCK GPIO39, MISO GPIO38, CS GPIO48, CD GPIO8
#   ARM CPU UART: TX GPIO9, RX GPIO10
#   Unassigned GPIO: GPIO15, GPIO16

uart:
  rx_pin: 9
  tx_pin: 10
  baud_rate: 115200
  stop_bits: 1
  data_bits: 8
  parity: NONE

text_sensor:
  - platform: wifi_info
    ip_address:
      name: ESP IP Address
      id: eth_ip

font:
  - file: "gfonts://Roboto"
    id: roboto
    size: 15

i2c:
  sda: 18
  scl: 17

display:
  - platform: ssd1306_i2c
    model: "SSD1306 128x64"
    address: 0x3C
    lambda: |-
      it.printf(0, 15, id(roboto), "IP: %s", id(eth_ip).state.c_str());

modbus:

modbus_controller:
  - id: ${devicename}_modbus
    address: 1
    update_interval: 5s

n30.yaml
substitutions:
  devicename: n30
  friendly_name: n30

packages:
  device: !include devices/kincony-n30.yaml

# Per-channel overrides. Uncomment and edit; !extend merges into the templated
# sensor by id (${devicename}_<chip>_<channel>_<current|power|energy>). Filters are appended
# after the template's own (multiply 0.001 for current, 0.1 for power).
# sensor:
#   # Offset one channel's power reading.
#   - id: !extend ${devicename}_1_5_power
#     filters:
#       - offset: -2.0
#
#   # Scale one channel's current (CT calibration).
#   - id: !extend ${devicename}_2_3_current
#     filters:
#       - multiply: 1.02
#
#   # Rename a channel.
#   - id: !extend ${devicename}_1_7_power
#     name: Office Power
#
#   # Hide an unused channel from Home Assistant.
#   - id: !extend ${devicename}_3_10_power
#     internal: true
#
#   # Average a noisy channel over 30s before publishing.
#   - id: !extend ${devicename}_1_2_power
#     filters:
#       - throttle_average: 30s

Downloads: n30.yaml, devices/kincony-n30.yaml, kincony-n30-chip.yaml, kincony-n30-channel.yaml

Overriding a single channel

To change one channel, without touching the template, add an !extend with the sensor's id to the board file. The id format is ${devicename}_<chip>_<channel>_<current|power|energy>.

Filters are added after the template's own filters (multiply: 0.001 for current, multiply: 0.1 for power).

sensor:
  # Offset one channel's power reading.
  - id: !extend ${devicename}_1_5_power
    filters:
      - offset: -2.0

  # Scale one channel's current (CT calibration).
  - id: !extend ${devicename}_2_3_current
    filters:
      - multiply: 1.02

  # Rename a channel.
  - id: !extend ${devicename}_1_7_power
    name: Office Power

  # Hide an unused channel from Home Assistant.
  - id: !extend ${devicename}_3_10_power
    internal: true

  # Average a noisy channel over 30s before publishing.
  - id: !extend ${devicename}_1_2_power
    filters:
      - throttle_average: 30s

Each of these was checked with esphome config. My board files have this block at the bottom, commented out.

The N30 also has a calibration factor for each channel, stored on the board itself (see the coefficients table below). That one only scales the reading. It cannot add an offset.

Modbus Reference

Everything below is from Kincony's N30 Energy RS485 Modbus Protocol, using the updated revision for ARM firmware V20_260305SP or newer. Where something is from my own boards, rather than the document, it is noted.

Communication

Setting Value Source
Protocol Modbus RTU over RS485 Kincony
Baud (RS485) 38400 Kincony
Baud (ESP32 to ARM UART, internal) 115200 Kincony's ESPHome YAML, and mine
Framing 8N1 My boards (not in the document)
Slave address 1 My boards (not in the document)
Read registers FC 0x03 (holding registers) Kincony
Write coil FC 0x05 Kincony
Write register FC 0x06 (single), FC 0x10 (multiple) Kincony

Measurement registers

Read with FC 0x03. Each chip has a 68 register block. Chip 1 starts at 100, chip 2 at 200, and chip 3 at 300. Chip 1 is the P1 connector, chip 2 is P2, and chip 3 is P3.

The doc does not explain “CDBA” float order. In ESPHome, these read correctly with U_DWORD_R (current), S_DWORD_R (power) and FP32_R (energy, temperature, power factor), which is what my config uses.

Offset Name Type Words Unit Scale Chip 1 Chip 2 Chip 3 Description
0 RMS_1 uint32 2 A 0.001 100 200 300 Channel 1 RMS current
2 RMS_2 uint32 2 A 0.001 102 202 302 Channel 2 RMS current
4 RMS_3 uint32 2 A 0.001 104 204 304 Channel 3 RMS current
6 RMS_4 uint32 2 A 0.001 106 206 306 Channel 4 RMS current
8 RMS_5 uint32 2 A 0.001 108 208 308 Channel 5 RMS current
10 RMS_6 uint32 2 A 0.001 110 210 310 Channel 6 RMS current
12 RMS_7 uint32 2 A 0.001 112 212 312 Channel 7 RMS current
14 RMS_8 uint32 2 A 0.001 114 214 314 Channel 8 RMS current
16 RMS_9 uint32 2 A 0.001 116 216 316 Channel 9 RMS current
18 RMS_10 uint32 2 A 0.001 118 218 318 Channel 10 RMS current
20 WATT_1 int32 (uint32 before V20_260305SP) 2 W 0.1 120 220 320 Channel 1 active power. Negative = reverse power
22 WATT_2 int32 (uint32 before V20_260305SP) 2 W 0.1 122 222 322 Channel 2 active power. Negative = reverse power
24 WATT_3 int32 (uint32 before V20_260305SP) 2 W 0.1 124 224 324 Channel 3 active power. Negative = reverse power
26 WATT_4 int32 (uint32 before V20_260305SP) 2 W 0.1 126 226 326 Channel 4 active power. Negative = reverse power
28 WATT_5 int32 (uint32 before V20_260305SP) 2 W 0.1 128 228 328 Channel 5 active power. Negative = reverse power
30 WATT_6 int32 (uint32 before V20_260305SP) 2 W 0.1 130 230 330 Channel 6 active power. Negative = reverse power
32 WATT_7 int32 (uint32 before V20_260305SP) 2 W 0.1 132 232 332 Channel 7 active power. Negative = reverse power
34 WATT_8 int32 (uint32 before V20_260305SP) 2 W 0.1 134 234 334 Channel 8 active power. Negative = reverse power
36 WATT_9 int32 (uint32 before V20_260305SP) 2 W 0.1 136 236 336 Channel 9 active power. Negative = reverse power
38 WATT_10 int32 (uint32 before V20_260305SP) 2 W 0.1 138 238 338 Channel 10 active power. Negative = reverse power
40 Energy_1 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 140 240 340 Channel 1 accumulated energy
42 Energy_2 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 142 242 342 Channel 2 accumulated energy
44 Energy_3 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 144 244 344 Channel 3 accumulated energy
46 Energy_4 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 146 246 346 Channel 4 accumulated energy
48 Energy_5 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 148 248 348 Channel 5 accumulated energy
50 Energy_6 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 150 250 350 Channel 6 accumulated energy
52 Energy_7 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 152 252 352 Channel 7 accumulated energy
54 Energy_8 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 154 254 354 Channel 8 accumulated energy
56 Energy_9 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 156 256 356 Channel 9 accumulated energy
58 Energy_10 float CDBA (uint32 1 kWh/LSB before V20_260305SP) 2 kWh 158 258 358 Channel 10 accumulated energy
60 Energy_Sum float CDBA (uint32 before V20_260305SP) 2 kWh 160 260 360 Sum of the chip's channels
62 RMS_V uint16 1 V 0.01 162 262 362 Voltage
63 Period uint16 1 Hz 0.01 163 263 363 Line frequency
64 TPS1 float 2 °C 164 264 364 Temperature
66 PF float 2 166 266 366 Power factor, 0-1

The document also lists aggregate data starting at register 1000 (sums for current, power and energy, averages for voltage and frequency, max for temperature), but does not give a layout for it.

Configuration register

Register Hex Function Read / Write Values
30 0x1E Bidirectional CT mode FC 0x03 / FC 0x06 0 = Disabled, 1 = Enabled

Coils

Written with FC 0x05. The document does not give the value to write. FF 00 works on mine (see the logs in the flashing post). The per-channel clear coils are given as ranges; 526 being channel 1 is implied, but not stated.

Address Hex Function
500 0x1F4 Warm reset
501 0x1F5 Save communication parameters to flash
503 0x1F7 Save calibration coefficients to flash
504 0x1F8 Clear coefficients (resets all to 1.0)
510 0x1FE Restore factory communication parameters
520 0x208 Clear all energy, chip 1
521 0x209 Clear all energy, chip 2
522 0x20A Clear all energy, chip 3
526-535 0x20E-0x217 Clear energy, chip 1 channels 1-10
536-545 0x218-0x221 Clear energy, chip 2 channels 1-10
546-555 0x222-0x22B Clear energy, chip 3 channels 1-10
586 0x24A Clear sum energy, chip 1
587 0x24B Clear sum energy, chip 2
588 0x24C Clear sum energy, chip 3

Calibration coefficients

Float (CDBA), 2 words each, default 1.0. Read with FC 0x03, written with FC 0x10. Write coil 503 afterwards to save them to flash.

Chip 1 is listed below. The document gives the chip 2 base as 3064, and chip 3 as 3128, with the same layout.

Address (chip 1) Hex Coefficient
3000 0xBB8 RMS1 factor
3002 0xBBA RMS2 factor
3004 0xBBC RMS3 factor
3006 0xBBE RMS4 factor
3008 0xBC0 RMS5 factor
3010 0xBC2 RMS6 factor
3012 0xBC4 RMS7 factor
3014 0xBC6 RMS8 factor
3016 0xBC8 RMS9 factor
3018 0xBCA RMS10 factor
3020 0xBCC WATT1 factor
3022 0xBCE WATT2 factor
3024 0xBD0 WATT3 factor
3026 0xBD2 WATT4 factor
3028 0xBD4 WATT5 factor
3030 0xBD6 WATT6 factor
3032 0xBD8 WATT7 factor
3034 0xBDA WATT8 factor
3036 0xBDC WATT9 factor
3038 0xBDE WATT10 factor
3040 0xBE0 ENERGY1 factor
3042 0xBE2 ENERGY2 factor
3044 0xBE4 ENERGY3 factor
3046 0xBE6 ENERGY4 factor
3048 0xBE8 ENERGY5 factor
3050 0xBEA ENERGY6 factor
3052 0xBEC ENERGY7 factor
3054 0xBEE ENERGY8 factor
3056 0xBF0 ENERGY9 factor
3058 0xBF2 ENERGY10 factor
3060 0xBF4 ENERGY SUM factor

Changes in V20_260305SP

  • Power (WATT) changed from uint32 to int32. Negative values are reverse power.
  • Energy changed from uint32 (1 kWh per count, max 65535 kWh) to float.
  • Added FC 0x06, and register 30 (bidirectional CT mode).

Bank 1 reads negative? L and N are backwards

This happened on both of my N30s.

The symptom

Every loaded channel on bank 1 reads negative watts. Bank 2 on the same board is positive. Volts and amps look normal. The CTs are all clamped the same direction, and the CT connectors are all plugged in the same way.

My N30, reading raw signed power (W), before the fix:

Ch Bank 1 Bank 2
4 0.0 6.8
5 -94.0 0.0
6 0.0 78.1
7 -389.9 0.0

Why it happens

Each BL0910 chip calculates real power from its CT current and its own voltage input. If L and N are swapped on a chip's voltage input, the voltage waveform it sees is upside down. The RMS volts still read a normal ~123 V, but every power reading on that chip comes out negated. From the readings alone, that looks the same as every CT on the bank being reversed.

I don't know if this is the board's terminal layout, or something else. Both boards, wired the same way, had bank 1 inverted and bank 2 correct.

The fix

With the power off, swap L and N on bank 1's voltage input.

These are the voltage inputs, one L / N pair per bank:

The N30's voltage input terminal block, labeled L1 N1 L2 N2 L3 N3

Same N30, same ports, after the swap:

Ch Bank 1 Bank 2
4 0.0 6.8
5 188.8 0.0
6 0.0 138.2
7 316.9 0.0

And the second board, bank 1, before and after the same swap:

Ch Before After
2 -244.5 243.3
3 -81.7 89.5
5 -157.1 156.3

The loads stayed on the same ports. Only the sign changed.